KBP Series Manual 41
Recirculaon Modes
Sequence of Operaon
DIP switches (SW #4, #7, & #8 in DIPSW 2) should be
set correctly for recirculaon mode. The Rinnai water
heater should be turned on.
Pump recirculaon begins when the water heater is
turned on. The Rinnai inlet and/or outlet thermistors
measure the water temperature.
The cycle will restart at the approximate me
intervals based on the applicaon (Cross over or
Dedicated mode, set temperature, and preset mode
ie. Comfort or Economy)
Rinnai Circ-Logic™ oers homeowners enhanced
convenience and energy eciency in home hot water
recirculaon systems with a dedicated return line or
cross over return using the included thermal by-pass
valve.
Circ-Logic™ has been designed to provide
homeowners with the ability to customize their
recirculaon systems based on such key variables as
length of recirculaon loop, piping insulaon, and the
homeowner's comfort and eciency preferences.
NOTE
Rinnai strongly recommends installing insulaon to
the hot water and dedicated return lines to decrease
the amount of heat loss .
Dedicated Mode
Maximum Pipe Length
(Hot Water Supply Line and Dedicated Return Line)
Pipe Diameter 3/4" 1/2"
Total 400 100
Dedicated return line will run from point of use
located farthest away from tankless water heater.
Less energy is consumed due to fewer pump
cycles
When the return water temperature reaches
approximately 12.6°F (7°C) below the selected
temperature seng, the water heater and pump
will turn o.
Dedicated mode requires that a dedicated line be
installed in the applicaon; Refer to Installaon of
Plumbing secon (Dedicated Mode Plumbing Diagram)
Dedicated Return Line:
Dip Switch sengs for Dedicated Mode (DIPSW 2)
Operaon SW 4 in SW 7 in SW 8 in
Pump o OFF OFF N/A
Dedicated Pipe OFF ON N/A
Economy N/A N/A OFF
Comfort N/A N/A ON
Rinnai
Temperature Seng
°F
Typical Pump ON
Intervals* (minutes)
Economy Comfort
140 18 9
135 20 10
130 22 11
125 24 12
120 28 14
115 32 16
110 38 19
108 40 20
106 44 22
104 48 24
102 52 26
100 56 28
98 62 31
Dedicated Mode Pump Intervals
* The pump will cycle on at these calculated
intervals which are based on the temperature
seng, insulaon, and esmated heat loss in the
system. The values for your installaon may vary.