Venng Guidelines

Do not use cellular core PVC/CPVC.
Do not use Radel, ABS, or galvanized material to
vent this appliance.
Do not combine vent components from dierent
manufacturers.
Vent diameter must not be reduced.
Do not connect the venng system with an
exisng vent or chimney.
Do not common vent with the vent pipe of any
other manufacturer’s water heater or appliance.
Rinnai water heaters can only be common vented
using a Rinnai cered common vent system.

This water heater is a direct vent water heater and
therefore is cered and listed with the vent
system. You must use vent components that are
cered and listed with the water heater model.
The vent system must vent directly to the outside
of the building and use outside air for combuson.
Avoid dips or sags in horizontal vent runs by
installing supports per the vent manufacturer’s
instrucons.
Support horizontal vent runs every four feet and
all vercal vent runs every six feet or in
accordance with local codes, beginning as close as
possible to the water heater to ensure no
movement and that the weight of the vent is
independently supported.
Venng should be as direct as possible with a
minimum number of pipe ngs.
Gasketed type vent connecons must be rmly
pressed together to form an air ght seal.
The vent piece connected to the water heater
must be secured with one self-tapping screw.

Refer to the instrucons of the vent system
manufacturer for component assembly
instrucons.
If the vent system is to be enclosed, it is suggested
that the design of the enclosure shall permit
inspecon of the vent system. The design of such
enclosure shall be deemed acceptable by the
installer or the local inspector.

If it becomes necessary to access an enclosed vent
system for service or repairs, Rinnai is not responsible
for any costs or dicules in accessing the vent
system. The warranty does not cover obtaining
access to a vent system in an enclosed environment.