KBP Series Manual 35
Vent Components and Assigned Equivalent Lengths:
The following ngs and accessories (by others) are cered for use with the abovemenoned condensing products:
IPEX (Purchased
separately )
196006 /197009
(3 Inch)
196021 /197021
(4 Inch)
(System 636)
PVC/CPVC- FGV
Concentric Vent Kit w/
vent screen
20
IPEX (Purchased
separately )
196985
(3 Inch)
196986
(4 Inch)
(System 636)
Low Prole
Terminaon Kit
5
Field Supplied
PVC/CPVC Sch. 40
Fings
-
3” and 4” SCH 40 (Solid
Core) PVC/CPVC TEE
w/ vent screen
5
Field Supplied
PVC/CPVC Sch. 40
Fings
-
3” and 4” SCH 40 (Solid
Core) PVC/CPVC 90° EL
w/ vent screen
5
Field Supplied
PVC/CPVC Sch. 40
Fings
-
3” and 4” SCH 40 (Solid
Core) PVC/CPVC 45° EL
w/ vent screen
2.5
IPEX (Purchased
separately )
196051
(3 Inch)
196052
(4 Inch)
Fricon t vent screen
(3” and 4”)
0
Field Supplied
PVC/CPVC Sch. 40
Fings
-
3” and 4” SCH 40 (Solid
Core) PVC/CPVC
Snorkel vent w/
vent screen
(2X90° EL + 1X45° EL)
15
Vent screens are not ULC S636 Cered.
Fricon t vent screens inside terminaon ng are used to avoid debris and/or small animals from entering vent.
Primer shall be used when installing System 636® and other PVC/CPVC products at temperatures below 32
O
F (0
O
C).
Primer is required in some jurisdicons regardless of temperature, verify with your local authority having jurisdicon.
Use only System 636 cements and primers with System 636 vent pipes.
For Schedule 40 PVC/CPVC, any glue and primer approved by your local authority having jurisdicon may be substuted.
Parts Informaon (connued)
Comments to this Manuals