Rinnai SUNMASTER Installation Manual Page 44

  • Download
  • Add to my manuals
  • Print
  • Page
    / 64
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 43
Rinnai Australia - 42 - Solar Split Systems Operating / Installation Manual
INSTALLATION PROCEDURE
Install Solar Collectors
Position and install the solar collectors in accordance with the section ‘INSTALLATION SOLAR
COLLECTORS”.
1. Position Storage Cylinder
Position the hot water storage cylinder on a level base in accordance with the section ‘STORAGE
CYLINDER LOCATION’.
2. Connect PTR Valve
Connect the PTR Valve in the location shown in the relevant diagram of Figures 27 to 30.
Leave the valve outlet pointing down. Tighten the valve using the spanner flats - never use the
valve body.
The PTR Valve must be adequate for the thermal loading applied to the storage cylinder. In the
case of gas boosted systems, the thermal load is applied only by the solar collectors. The
continuous flow hot water heater does not apply thermal load to the storage cylinder. The potential
solar output for the solar collectors at PTR Valve relief conditions is listed in Table 3.
The PTR Valve pressure ratings vary according the cylinder specifications. The maximum heater
input rating is 10.0 kW. The PTR valve rating MUST EXCEED the total input from the solar
collectors. If it does not, the PTR valve MUST be exchanged for a model of higher capacity.
For example, for a gas boosted solar system with 3 x SP200A collectors, the thermal load is 3 x
1.25 = 3.75 kW. This is less than 10.0 kW, hence the supplied PTR valve is of sufficient capacity.
Use Teflon thread tape on the valve, never use hemp or other sealing materials. Ensure the tape
does not protrude past the end of the thread, which could result in it hanging over the end of the
thread and blocking the water passage through the valve.
3. Mount Gas Booster
Mount the gas booster in accordance with the section ‘GAS BOOSTER LOCATION & MOUNTING’.
4. Connect Fittings and Mount Pump Assembly
Connect fittings and pipe work as shown in the relevant diagram in Figures 27 to 30. Remove
cover of pump box and attach pump box to cylinder using screws provided. DO NOT connect the
power lead to power supply at this stage.
5. Install and Connect Flow and Return Pipe Work
Connect flow and return pipe work between storage cylinder and solar collector. Ensure that
suitable pipe and insulation is used as described in the section "WATER PIPES".
6. Connect Temperature Sensor Leads
The hot (longer) temperature sensor lead should be fitted into
the air bleed / hot sensor lead assembly at the collector hot
return connection as shown in Figures 25 to 26. It must be
sealed in place with thermoplastic putty or silicone.
Run the lead down the solar return pipe and connect it to the
connection within the pump and controller assembly as shown
in the diagram. Ensure the lead is protected from light. Figure
34 - Temperature Sensor Leads
The cold (shorter) temperature sensor lead should be fitted as
shown in the relevant diagram in Figures 27 to 30. It must be
sealed in place with thermoplastic putty or silicone. The plug is
then connected to the pump and controller assembly as shown
in the diagram.
Replace Pump Assembly Cover.
IT IS IMPORTANT THAT THESE PROBES ARE INSTALLED AS SPECIFIED. FAILURE
TO DO SO WILL LEAD TO MALFUNCTION OR LACK OF HOT WATER.
cold sensor connection
in pump box.
hot sensor connection
in pump box.
cold sensor lead
connection
hot sensor lead
connection
Figure 3 - Temperature Sensor Leads
NOTE
INSTALLATION & MAINTENANCE - GAS BOOSTED SYSTEMS
Page view 43
1 2 ... 39 40 41 42 43 44 45 46 47 48 49 ... 63 64

Comments to this Manuals

No comments