Rinnai Australia - 26 - Solar Split Systems Operating / Installation Manual
FRAMED INSTALLATIONS - CYCLONE FRAME
Assemble cyclone frame and mount collectors as described in instructions provided with cyclone
frame kit.
COMMERCIAL INSTALLATIONS
Commercial system comprise of multiple of 2-3 collectors joined together. Figure 22 shows the roof
spacing required for the collector sets.
Figures 23 and 24 shows the flow and return piping layout for multiple collector sets.
Pipe sizing shown in table below:
Table 8 - Commercial Pipe Sizing
Total collectors in array
Up to 10 20 30 40 50 60 70 80 90 100
Pipe sizing for solar flow and
return manifolds
DN20 DN20 DN25 DN32 DN32 DN32 DN40 DN40 DN40 DN50
Pump
20-60N 20-60N 20-60N 25-80N 25-80N 25-80N 25-80N 25-80N 25-80N 25-80N
130--
2 604020
3 100 100 100 100 100 100 100 100 100 100
Maximum pipe run in collector circuit (m)
Pump speed
PIPE AND PUMP SIZING CHART - COMMERCIAL ARRAYS
That the combined length of flow and return piping for each collector set is
approximately the same. This will result in even flow to all collectors and
optimum performance.
NOTE
INSTALLATION OF SOLAR COLLECTORS