RH180 Manual 21
Installaon of Plumbing
A manual valve must be placed in the water inlet
connecon to the water heater before it is connected
to the water line. Unions may be used on both the
hot and cold water lines for future servicing and
disconnecon of the unit.
DO NOT
Do not introduce toxic chemicals such as those
used for boiler water treatment to the potable
water used for space heang.
MUST DO
The piping (including soldering materials) and
components connected to this appliance must be
approved for use in potable water systems.
Purge the water line to remove all debris and air.
Debris will damage the water heater.
If the appliance will be used as a potable water
source, it must not be connected to a system that
was previously used with a nonpotable water
heang appliance.
Ensure that the water lter on the water heater is
clean and installed.
Piping Requirements
Temperature-Pressure Relief Valve
Requirements
Install the Temperature-Pressure Relief (T&P) Valve
according to these instrucons.
This water heater is provided with a combinaon
temperature-pressure relief valve. For safe operaon
of the water heater, the relief valve(s) must not be
removed from its designated point of installaon or
plugged.
(Ce chaue-eau est équipé d’une soupape de
décharge. Pour assurer le fonconnement sécuritaire
du chaue-eau, ne pas rerer ni obturer cee
soupape de décharge.)
An approved Temperature-Pressure Relief Valve is
required by the American Naonal Standard (ANSI
Z21.10.3) for all water heang systems, and shall be
accessible for servicing.
DO NOT
Do not plug the T&P valve and do not install any
reducing ngs or other restricons in the relief
line. The relief line should allow for complete
drainage of the T&P valve and the line.
Do not place any other type valve or shut o
device between the relief valve and the water
heater.
MUST DO
The T&P valve must comply with the standard for
Relief Valves and Automac Gas Shuto Devices for
Hot Water Supply Systems ANSI Z21.22 and /or the
standard Temperature, Pressure, Temperature and
Pressure Relief Valves and Vacuum Relief Valves,
CAN1-4.4.
The T&P valve must be rated up to 150 psi and to
at least the maximum BTU/hr of the appliance.
The discharge from the T&P Valve should be piped
to the ground or into a drain system to prevent
exposure or possible burn hazards to humans or
other plant or animal life. Follow local codes.
Water discharged from the relief valve could cause
severe burns instantly, scalds, or death.
The Temperature-Pressure Relief Valve must be
manually operated once a year to check for correct
operaon.
INFORMATION
If a T&P discharges periodically, this may be due to
thermal expansion in a closed water supply
system. Contact the water supplier or local
plumbing inspector on how to correct this
situaon. Do not plug the relief valve.