20 RH180 Manual
Checklist for Combuson Air and
Venng Requirements
□ Verify proper clearances around the vents .
□ Ensure that the Combuson Air Requirements are
followed that will provide sucient combuson
air for the appliance.
□ Ensure you have used the correct venng
products for Category 1 and that you have
completely followed the venng manufacturer’s
installaon instrucons and these installaon
instrucons. All installaons must be vented in
accordance with Naonal Fuel Gas Code NFPA
54/ANSI Z223.1 - latest edion and the
requirements of state or local codes. In Canada,
the furnaces must be vented in accordance with
the Naonal Standard of Canada, CAN/CSA
B149.1 and CAN/CSA B149.2 - latest edions and
amendments and the codes of the local ulity or
other authority having jurisdicon.
□ All horizontal vent runs must be sloped up away
from the water heater a minimum of 1/4 “ (6 mm)
per foot.
□ Verify that the vent terminaon clearances are
followed.
□ Verify that there is adequate combuson air.