Rinnai Australia - 10 - Rinnai Luminaire® Outdoor Gas Fire - Operation and Installation Manual
Open Fronted Radiant / Convector Rinnai Luminaire Outdoor Gas Fire
with manual control.
Comes in 3 designs:
• Freestanding table top unit
• Open One sided cabinet (with optional glass bi-fold doors)
• Open Two sided see-through unit (with optional glass bi-fold doors)
Gas Type: Universal LPG / NG
Suitability: This is a permanently fixed luminous effect appliance
outdoor areas only. Not to be used for cooking food preparation or food
warming.
Burner 304 stainless steel tube burner
Combustion Method Aerated bunsen type burner
Data Plate Left hand side of burner under granite cover
Gas Control
Gas control valve consisting of an inlet connection, Piezo ignitor, thermocouple flame
failure and manual control knob.
The valve operating sequence is to turn the valve to the pilot position before lighting
the main burner. Only, when the pilot has established can the gas valve be turned to
high and low combustion settings.
Gas Connection (ULPG)
9 kg ULPG Cylinder: Quick Disconnect (QDC)
‘Rectus Type 21’
NG: 5/8” UNF flared connection to
NG Regulator
Ignition System Intermittent pilot
Input ULPG: 45-25 MJ/h (High to Low) NG: 41-22 MJ/h (High to Low)
Pilot
SIT
®
single injector pilot assembly with fixed aeration and replaceable fixed pilot
injector for NG and ULPG. Pilot assembly also contains a pilot ignition electrode and
thermocouple for flame failure.
Internal Piping
Burner is supplied through an aluminium pipe from the gas control to the burner
injector block. Pilot burner is supplied gas via aluminium pipe directly from the gas
control.
Pressure Test Point Incorporated into main burner injector block measuring burner pressure
Regulator Pressure regulator with exchangeable spring for NG
Safety Devices Light to Pilot and Flame Failure Safety Device (FFD)
Flue Gas Outlet Top Louvre discharge (Cabinet models only)
Weight Burner Assembly: 20 kg Body Assembly: 30 kg (Burner + Body: 50 kg)
ULPG NG
Pilot Injector # 35 # 62
Main Injector 1.90 mm 3.60 mm
Test Point Pressure (High) 2.45 kPa 0.43 kPa
Test Point Pressure (Low) 0.80 kPa 0.13 kPa
Minimum Supply Pressure 2.50 kPa 1.13 kPa
Maximum Supply Pressure 3.50 kPa 3.50 kPa
Include Dimensions
With Fascia & Doors - mm
(fascia add 40 mm)
SPECIFICATIONS