RDV3611 Installation Manual: 11156-A 01-12 | 5
Location
The main points governing location are flueing and warm air distribution. The heater must
not be installed where curtains or other combustible materials could come into contact with
the appliance. In some cases curtains may need restraining.
Enclosure dimensions
The heater must be positioned on
a flat level surface. For installations
further up the wall, the heater
needs to be supported, either
construct a base using board, or
support with joists.
A 25 mm clearance is required
around the unit (sides and back).
The 540 mm minimum dimension
will give a 25 mm clearance (plus)
from the back of the unit.
If installing the Symmetry Heat
Transfer Kit, allow an additional
side clearance of 250 mm. This
clearance is required to ensure
the ducting does not come into
contact with the fire.
1100 - 1125 mm
850 mm min.
540 mm min.
1295 mm
1830 mm
915 mm
These are the minimum dimensions required if using the width, height, and depth
dimensions above.
Enclosure dimensions in a corner
Page view 4