Rinnai CVent 12
Venng Guidelines
DO NOT
Do not install in separate distribuon systems. All
water heaters common vented must be in the
same hot and cold plumbing manifolds and must
not exceed 8 units.
Do not use PVC, CPVC, ABS or galvanized material
for the exhaust vent. CVent must be used on the
exhaust.
Do not combine vent components from dierent
manufacturers.
Vent diameter must not be reduced.
Do not connect the venng system with an
exisng vent or chimney.
Do not common vent with the vent pipe of any
other type of water heater or appliance.
Do not install the water heater in an area of
negave pressure.
Do not install the water heater, venng, and vent
terminaon(s) in any areas where the air may
contain corrosive compounds.
MUST DO
• The water heater dip switch seng must always
be set to long vent (#1 in set of tan switches set to
OFF).
This water heater is a direct vent water heater and
therefore is cered and listed with the vent
system. You must use vent components that are
cered and listed with the water heater model.
The vent system must vent directly to the outside
of the building and use outside air for combuson.
Avoid dips or sags in horizontal vent runs by
installing supports per the vent manufacturer’s
instrucons.
Support horizontal vent runs a minimum of every
four feet and all vercal vent runs a minimum of
every six feet.
Venng should be as direct as possible with a
minimum number of pipe ngs.
Vent connecons must be rmly pressed together
so that the gaskets form an air ght seal.
Install an appliance adapter which contains a
check valve onto each water heater. Use only the
check valve specied in this manual. Do not
aempt to build your own system.
The air intake appliance adapter connected to the
water heater must be secured with one self-
tapping screw.
Check and clean the header check valve every 12
months according to the maintenance instrucons
in this manual.
Set the temperature seng on all water heaters
being common vented to the same temperature.
INFORMATION
Unless recovering a tank, Rinnai recommends
installing an MSB controller when common
venng and where water heaters are in a manifold
system.
For assembly details, refer to the Ubbink
Installaon and Assembly Instrucons located in
the appendix of this manual.
Rinnai recommends replacing the check valve
when replacing the water heater.
The Ubbink Polypropylene CVent can be used on both the combustion air and exhaust.
Field supplied PVC material can only be used on the combustion air side and MUST NOT
be used for the exhaust.
WARNING